Electrical & Instrumentation · Free tool
Cable sizing calculator
Size a low-voltage copper or aluminium cable the way an engineer does: check voltage drop and short-circuit withstand, then confirm the current rating. Every step of the working is shown.
Minimum cable size
16 mm²
copper, XLPE
Set by voltage drop, before the current rating check below.
- Design current
- 40 A
- Min. rating
- 50 A
- Voltage drop
- 2.02%
- Drop (volts)
- 8.1 V
Minimum area each check needs
Full bar = the chosen standard size (16 mm²).
For your installation method and conditions. Must be at least 50 A.
- Short-circuit capability not checked. Enter the prospective fault current and clearing time to include it.
The working
Equation numbers refer to IEEE Std 525-2007, Annex C.
- Input40 A
Design current Ib
Load entered in amperes
- C.2.250 A
Required cable ampacity
1.25 × 40 A
- C.312 V
Allowed voltage drop
3% × 400 V
- C.510.771 mm²
Minimum area for voltage drop
ρ × √3 × 80 m × 40 A / 12 V × [1 + α(90 − 20)] × 1.02 × 1.04, copper ρ = 0.017241 Ω·mm²/m, α = 0.00393/°C
- C.41.4575 mΩ/m
Resistance of 16 mm² at 90 °C
0.017241 / 16 × [1 + 0.00393(90 − 20)] × 1.02 × 1.04
- C.2b8.08 V (2.02%)
Voltage drop with 16 mm²
√3 × 80 m × 40 A × R
Need this cable supplied? Send the result to us for a quote.
Request a quoteHow this calculator works
- Three checks
- A cable must carry the load current without overheating (ampacity), deliver enough voltage at the far end (voltage drop), and survive a fault until the protection clears it (short circuit). The largest size any check needs is the answer. Method: IEEE Std 525-2007, Annex C.
- Voltage drop
- Conductor resistance is calculated from the metal's resistivity, corrected to operating temperature and for stranding (Eq. C.4). The drop counts both conductors on single phase and DC, and √3 on three phase. Typical limits: 3% for a feeder or a final circuit, 5% in total.
- Short circuit
- During a fault the conductor heats from its operating temperature to the insulation's limit: 250 °C for XLPE, 150 °C for PVC. Eq. C.15 gives the minimum area for the fault current and clearing time.
- Current rating
- The cable's current rating must be at least 1.25 times the load (C.2.2). Ratings depend on how the cable is installed, so look up the recommended size in ZS 772-1 (The wiring of premises) and enter it to complete the check. Built-in ratings are coming.
- Standard sizes
- Results step through the conductor sizes in ZS 688, the cable standard made compulsory in Zambia by Statutory Instrument No. 59 of 2013.
- Limits
- Low voltage only. Reactance is left out, which is accurate below about 107 mm²; above that the tool warns you. Motor starting, harmonics and parallel cables need a full design.
Tools on this site are for guidance and learning. Results and examples must be checked by a qualified engineer against the applicable standards before any installation or design decision.